DZ116(MS116) Motor starter Motor protector
MS116-10 motor starter
Application covers motors up to 16A (7.5kW)
Local isolator
Protection against overload, short circuit, phase fault and cable and wire fault
These motor starters can be used with contactors
Provide accessories from auxiliary/signal contact to undervoltage release. With the adapter, the contactor can be used to easily build the motor starter combination.
Model and name
Trip Diagram
Specifications
Type | Dz116 | Dz132 | DZ450/451 | DZ495/496/497 | |
Rated insulation voltage Ui | IECEN 60947 VAC | 690 | |||
CSA/UL/NEMA VAC | 600 | ||||
Rated operating voltage Ue V | 690AC | ||||
Rated impulse withstand voltage Uimp KV | 6 | ||||
Rated operating current le A | 32A | 32A | 50A | 100 A | |
Rated continuous heating current Ith A | 32A | 32A | 50A | 100A | |
Rated frequency Hz | 50/60 | ||||
Current setting range le A | 0.1-32 | 0.1-32 | 11-50 | 28-100 | |
Short to the breaking capacity le 400V | Max50kA | Max100kA | Max50kA | MaxWOkA |
Specifications
Type | A…ACurrent setting range | Leu 400V AC. kA Short circuit breaking capacity | Rated instantaneous short circuit current | |||
DZ116 |
0.16 |
0.10.. |
0.16 | 50 |
1.25. |
.1.87 |
DZ116 |
0.25 |
0.16.. |
0.25 | 50 |
1.95. |
.2.92 |
DZ116 |
0.4 |
0.25.. |
0.40 | 50 |
3.12. |
.4.68 |
DZ116 |
0.63 |
0.40.. |
0.63 | 50 |
4.91. |
.7.37 |
DZ116 |
1.0 |
0.63.. |
1.00 | 50 |
9.20. |
.13.8 |
DZ116 |
1.6 |
1.00.. |
1.60 | 50 |
14.7. |
.22.1 |
DZ116 |
2.5 |
1.60.. |
2.50 | 50 |
23.0. |
.34.5 |
DZ116 |
4.0 |
2.50.. |
4,00 | 50 |
40.0. |
.60.0 |
DZ116 |
6.3 |
4.00.. |
6.30 | 50 |
63.0. |
.94.5 |
DZ116 |
10 |
6.30.. |
10.0 | 50 |
120. |
.180 |
DZ116 |
12 |
8.00.. |
12.0 | 25 |
144. |
.216 |
DZ116 |
16 |
10.0.. |
16.0 | 16 |
192. |
,288 |
DZ116 |
20 |
16.0.. |
20.0 | 15 |
240. |
.360 |
DZ116 |
25 |
20.0.. |
25.0 | 15 |
300. |
.460 |
DZ116 |
32 |
25.0.. |
32.0 | 10 |
384. |
.576 |
The external fixing dimensions